5.4
Screwing the transport units together
NOTICE
Material damage caused by mechanical pressure on components
Stress that occurs during transport may exert mechanical pressure on the components.
Material damage can result.
● Line the cabinets up precisely with each other in order to avoid shearing forces when the
base units are screwed together.
● Install the converter only on a level and horizontal surface.
Screwing cabinets together
Use the mounting materials provided to screw the cabinets together. Proceed as follows to
screw the cabinets together:
1. Align the cabinets.
2. Insert the M10 screws through the mounting holes at the upper and lower sides of the
cabinet. The arrangement of the mounting holes is provided in the dimension drawing.
Select a suitable screw length depending on the location.
3. Place the washers and spring washer onto the screw.
4. Screw the transport units together using the nuts with a torque of 50 Nm.
5.5
Connecting to the foundation
Preparatory steps
1. Ensure that access to the holes in the bottom of the cabinets is unobstructed.
Securing the cabinet to the floor
The following details are specified in the dimension drawing:
● Mounting holes
● Mounting dimensions
● Distance between the cabinet top and the room ceiling
Holes are provided for M12 screws for securing the cabinet to the foundation.
Install the transportation units in accordance with the specifications provided in the
accompanying dimension drawings in "Layout diagrams and dimension drawings".
Installation
5.5 Connecting to the foundation
SINAMICS GM150 6SL3835-2LN44-2AA0
78
Operating Instructions Rev.201910281250 MUSTER
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0