Technical data
7.5 Technical data, 200 V inverters
Power Module PM240-2
76
Hardware Installation Manual, 01/2017, A5E33294624B AE
Table 7- 8
PM240-2, IP 20, frame size C, 3 AC 200 V … 240 V
Article number without filter
Article number with filter
6SL3210-1PC22-2UL0
6SL3210-1PC22-2AL0
6SL3210-1PC22-8UL0
6SL3210-1PC22-8AL0
LO base load power
5.5 kW
7.5 kW
LO base load input current
28.6 A
36.4 A
LO base load output current
22.0 A
28.0 A
HO base load power
4 kW
5.5 kW
HO base load input current
22.8 A
28.6 A
HO base load output current
17.5 A
22.0 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
50 A
3NA3820 (50 A)
50 A
Power loss
0.2 kW
0.26 kW
Required cooling air flow
18.5 l/s
18.5 l/s
Weight without filter
5.0 kg
5.0 kg
Weight with filter
5.2 kg
5.2 kg
Table 7- 9
PM240-2, PT, frame size C, 3 AC 200 V … 240 V
Article number without filter
Article number with filter
6SL3211-1PC22-2UL0
6SL3211-1PC22-2AL0
6SL3211-1PC22-8UL0
6SL3211-1PC22-8AL0
LO base load power
5.5 kW
7.5 kW
LO base load input current
28.6 A
36.4 A
LO base load output current
22.0 A
28.0 A
HO base load power
4 kW
5.5 kW
HO base load input current
22.8 A
28.6 A
HO base load output current
17.5 A
22.0 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
50 A
3NA3820 (50 A)
50 A
Power loss
0.2 kW
1)
0.26 kW
2)
Required cooling air flow
18.5 l/s
18.5 l/s
Weight without filter
5.0 kg
5.0 kg
Weight with filter
5.2 kg
5.2 kg
1)
approx. 0.2 kW through the heatsink
2)
approx. 0.15 kW through the heatsink