Technical data
7.6 Technical data, 400 V inverters
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
83
Table 7- 17 PM240-2, PT, Frame Size B, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3211-1PE21-8UL0
6SL3211-1PE21-8AL0
LO base load output
7.5 kW
LO base load input current
22.2 A
LO base load output current
18.0 A
HO base load output
5.5 kW
HO base load input current
19.8 A
HO base load output current
13.7 A
Fuse according to IEC
Fuse according to UL, class J
3NA3812 (32 A)
35 A
Power loss
0.2 kW
1)
Required cooling air flow
9.2 l/s
Weight without filter
3.6 kg
Weight with filter
3.9 kg
1) approx. 0.16 kW through the heatsink
Table 7- 18 PM240-2, IP20, Frame Size C, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3210-1PE22-7UL0
6SL3210-1PE22-7AL0
6SL3210-1PE23-3UL0
6SL3210-1PE23-3AL0
LO base load output
11.0 kW
15.0 kW
LO base load input current
32.6 A
39.9 A
LO base load output current
26.0 A
32.0 A
HO base load output
7.5 kW
11.0 kW
HO base load input current
27.0 A
36.0 A
HO base load output current
18.0 A
26.0 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
50 A
3NA3820 (50 A)
50 A
Power loss
0.3 kW
0.37 kW
Required cooling air flow
18.5 l/s
18.5 l/s
Weight without filter
4.7 kg
4.8 kg
Weight with filter
5.3 kg
5.4 kg