Using a Control Supply Module
If you are using a Control Supply Module, apply the 24 V supply directly via the 24 V busbars.
The electronic current limiting function integrated in the Control Supply Module protects the
busbar system when a fault occurs. You can connect additional loads via the 24 V terminal
adapter.
Note
Cables with a cross-section of 2.5 mm
2
If you use cables with a cross-section of 2.5 mm
2
, no additional protection is required on the 24
V side for the following cable types:
● Cables of the XLPE type
● Cables of the EPR type
● Cable with a similar quality and with a thermal stability of up to 90 °C
&RQWURO
6XSSO\
0RGXOH
0
0
0 0
0
;
9
$GDSWHU
0RGXOH
$GDSWHU
0RGXOH
/LQH
0RGXOH
&8
PP
)
Figure 8-1
Example of a 24 V supply with Control Supply Module
When selecting the miniature circuit breakers, you must take into account the following
standards:
EN 61800-5-1, EN 60204-1, IEC 60364-5-52, IEC 60287-1 to -3, EN 60228 and UL 508C.
Requirements for cables:
● Maximum ambient temperature: 55 °C
● Maximum conductor temperature limit: 70 °C for operation with rated load current
● Maximum cable lengths:
– 30 m for supply cables
– 30 m for signal cables
Control cabinet design
8.3 24 V DC supply voltage
Manual, 06/2019, 6SL3097-5AW00-0BP1
129
Summary of Contents for Sinamics S120M
Page 2: ......
Page 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 185: ......