Note
Mounting the 24 V terminal adapter on the component
The 24 V terminal adapter should be mounted to the left of the component located at the far left;
if it is positioned anywhere else, there may not be enough space for the red 24 V jumpers.
If necessary, the 24 V terminal adapter can also be positioned on the right for 50 mm and
100 mm modules.
WARNING
Electric shock if the cutout in the protective cover has been broken out
Live components are exposed and accessible if the 24 V terminal adapter or the DC link infeed
adapter are removed. Touching live components can result in death or serious injury.
● Replace the protective cover with the broken out cutouts with a new protective cover
(Article No.: 6SL3162-3AC00-0AA1).
Control cabinet design
8.3 24 V DC supply voltage
134
Manual, 06/2019, 6SL3097-5AW00-0BP1