The fuses to protect the conductors of the hybrid cable are integrated in the Adapter Module
600.
WARNING
Electric shock when replacing a fuse
Because of the DC link capacitors, a hazardous voltage is present for up to five minutes after
the power supply has been switched off.
Contact with live parts can result in death or serious injury.
● Switch the power supply off before replacing the fuse.
● Wait at least 5 minutes after switching off.
● Before starting any work, also check that the system is in a voltage-free state by measuring
at the DC link terminals DCP and DCN.
● Only use the following replacement fuses:
– SIBA
– Type URZ 14 x 51 mm, gR 800 VDC, 32 A
– Art. No. 5012006
– Siemens article number: 6SL3566-7DA00-0AA0.
Replacing a fuse in the AM600
①
Fixing screws
②
Fan cover
③
Fuses
Figure 9-3
Replacing a fuse in the AM600
Service and maintenance
9.2 Replacing components
Manual, 06/2019, 6SL3097-5AW00-0BP1
161
Summary of Contents for Sinamics S120M
Page 2: ......
Page 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 185: ......