Commissioning
5.5 First commissioning
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
167
NOTICE
A filter at the motor end must be entered in p0230 (option L08 – motor reactor: p0230 = 1,
option L10 – dV/dt filter with Voltage Peak Limiter: p0230 = 2, option L15 – sinusoidal filter:
p0230 = 3). Motor control will not otherwise function properly.
When p0230 = 4 "Sinusoidal filter, third-party", a separate sinusoidal filter can be entered.
An input screen then appears in which the specific filter can be entered.
Basic commissioning: Motor identification
)
)
)
)
)
)
)
)
)
)
^9(&725`0RWRULGHQWLILFDWLRQ
6WDWLRQDU\DQGURWDWLQJ
6HOHFWWKHW\SHRILGHQWLILFDWLRQ
2QO\VWDWLRQDU\
1RLGHQWLILFDWLRQ
+HOS
2.
^9(&725`0RWRULGHQWLILFDWLRQ
127(
6WDUWWKHGULYH
ZLWK/2&$/DQG21NH\
+HOS
$ERUW
Selecting motor identification
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
Stationary measurements increase control
performance as deviations in the electrical
characteristic values are minimized on
account of deviations in the material
properties and manufacturing tolerances.
Rotary measurements determine the data
required (e.g. moment of inertia) for setting
the speed controller. They also measure
the magnetization characteristic and rated
magnetization current of the motor.
To activate this function, press the LOCAL
key (wait until the LED in the LOCAL key
lights up) and then ON.
If motor identification is not carried out, the
motor controller is using the motor
characteristic values calculated from the
type plate data rather than the measured
values.
Note
When motor identification is complete, press the OFF key to cancel the power-on inhibit.