9.4.3.3
Checking hoisting solenoids and security bolts
● Check the hoisting solenoids and security bolts at regular intervals.
● Replace defective hoisting solenoids and security bolts before (re)commissioning.
9.4.3.4
Checking the plug connections.
Regularly check the plug connections to ensure they are seated correctly and the contacts are
not corroded.
Note
The fiber-optic cables for the gating boards must be properly inserted in the connectors.
9.4.3.5
Checking the filter mats
● Check the air filters in the cabinet doors for pollution.
● Clean the filter mats or replace them if the air flow is obstructed.
See also
9.4.3.6
Checking the cable and screw terminals
● Check the cable and screw terminals regularly to ensure that they are secure.
● Tighten the screws if necessary. When doing this, comply with the specified torques
● Check the cabling for defects.
● Replace any defective parts immediately.
9.4.3.7
Inspecting door limit switches
● Inspect the door limit switches regularly for contamination and corrosion.
● Also verify that the the door limit switches function correctly at regular intervals.
Maintenance
9.4 Preventive maintenance
SINAMICS SH150 6SL3805
Operating Instructions 05/2020
93
Summary of Contents for SINAMICS SH150
Page 2: ...19 06 2020 09 42 V14 00 ...
Page 42: ...Description 3 9 Interfaces SINAMICS SH150 6SL3805 42 Operating Instructions 05 2020 ...
Page 56: ...Preparations for use 4 5 Storage SINAMICS SH150 6SL3805 56 Operating Instructions 05 2020 ...
Page 116: ...Spare parts SINAMICS SH150 6SL3805 116 Operating Instructions 05 2020 ...
Page 120: ...Service Support SINAMICS SH150 6SL3805 120 Operating Instructions 05 2020 ...
Page 126: ...Quality documents SINAMICS SH150 6SL3805 126 Operating Instructions 05 2020 ...
Page 128: ...Additional documents SINAMICS SH150 6SL3805 128 Operating Instructions 05 2020 ...
Page 131: ......