● Only qualified personnel or personnel supervised by responsible, skilled specialists are
allowed to carry out basic planning and all work on the device.
● During shipping, specific transport conditions are adhered to.
● Assembly is performed according to assembly instructions. Separate cabinet units are
connected properly (cables and busbars).
● All instructions for EMC-compatible installation, cabling, shielding, grounding, and for
adequate auxiliary power supply are to be observed.
● Commissioning is only to be performed by qualified personnel trained for that purpose in
accordance with the commissioning instructions.
● System configuration is carried out by an experienced system integrator. Additional system
components - such as circuit-breaker, transformer, cables and motor - are coordinated and
harmonized with one another for drive operation.
● The device is only operated in conjunction with the engineered components.
● Different operating modes, overloads, load cycles, and differing environmental conditions
are permitted only after special arrangement with the manufacturer.
Make use of the support and services offered by the relevant service center for planning,
installation, commissioning, and servicing work. You can find the relevant contact person under
"Service & Support (Page 119)".
2.7.2
Grounding concept
Draw-up a grounding concept and integrate the device into this concept. The grounding
concept must take into consideration national provisions and system specifics. Ensure that the
following criteria are fulfilled:
● At the installation site, the various subunits must be screwed together to establish a good
electrical connection between them.
● If shield busbars are provided, these must be connected together.
● The protective grounding conductor must be connected to the system the grounding point.
Select the highest cross-section of the protective grounding conductor from one of the
following variants:
– According to local wiring regulations
– Calculated according to IEC 60364-5-54, 543.1
– Half a phase conductor cross-section
Safety instructions
2.7 Information for persons responsible for plants and systems
SINAMICS SH150 6SL3805
Operating Instructions 05/2020
19
Summary of Contents for SINAMICS SH150
Page 2: ...19 06 2020 09 42 V14 00 ...
Page 42: ...Description 3 9 Interfaces SINAMICS SH150 6SL3805 42 Operating Instructions 05 2020 ...
Page 56: ...Preparations for use 4 5 Storage SINAMICS SH150 6SL3805 56 Operating Instructions 05 2020 ...
Page 116: ...Spare parts SINAMICS SH150 6SL3805 116 Operating Instructions 05 2020 ...
Page 120: ...Service Support SINAMICS SH150 6SL3805 120 Operating Instructions 05 2020 ...
Page 126: ...Quality documents SINAMICS SH150 6SL3805 126 Operating Instructions 05 2020 ...
Page 128: ...Additional documents SINAMICS SH150 6SL3805 128 Operating Instructions 05 2020 ...
Page 131: ......