8.6.3.3
Diagnostics via parameters
Diagnostic parameters for the device status
r0002
Drive status
Display of drive status
r0046
Missing drive enable signals
Display of the missing enable signals that prevent the drive control from being commissioned
Bit
Signal name
0-signal
1-signal
00
OFF1 enable missing
No
Yes
01
OFF2 enable missing
No
Yes
02
OFF3 enable missing
No
Yes
03
Enable run missing
No
Yes
05
External power-on inhibit active
No
Yes
06
Commissioning not yet complete
No
Yes
09
Infeed enable missing
No
Yes
10
Ramp-function generator enable missing
No
Yes
11
Ramp-function generator start missing
No
Yes
12
Setpoint enable missing
No
Yes
13
PSA pulse inhibit due to undervoltage
No
Yes
14
Operation enable from automatic restart function
No
Yes
16
OFF1 internal enable missing
No
Yes
17
OFF2 internal enable missing
No
Yes
18
OFF3 internal enable missing
No
Yes
19
Pulse enable internal missing
No
Yes
24
Motor data set changeover active
No
Yes
25
Function bypass active
No
Yes
26
Drive inactive or not operational
No
Yes
r0050
Active command data set (CDS)
Display of the active command data set (Command Data Set, CDS)
Bit
Signal name
0-signal
1-signal
00
CDS effective, bit 0
No
Yes
01
CDS effective, bit 1
No
Yes
02
CDS effective, bit 2
No
Yes
03
CDS effective, bit 3
No
Yes
You can find additional notes in the parameter description of parameters p0810, p0811, r0836 in the List Manual.
The command data set selected via the binector inputs (e.g. p0810) is displayed via r0836.
Operation
8.6 Fault and system messages
SINAMICS SM150 6SL3845-2NN41-8AD0