Parameter list
8.1 Introduction to parameters
SINAMICS V20 Converter
196
Operating Instructions, 10/2019, A5E34559884-012
Access level (P0003)
Defines the level of user access to parameter sets.
Access level Description
Remarks
0
User-defined
parameter list
Defines a limited set of parameters to which the end user has ac-
cess. See P0013 for details on use.
1
Standard
Allows access into most frequently used parameters.
2
Extended
Allows extended access to more parameters.
3
Expert
For expert use only.
4
Service
Only for use by authorized service personnel, password protected.
Data type
The data types available are shown in the table below.
U8
8-bit unsigned
U16
16-bit unsigned
U32
32-bit unsigned
I16
16-bit integer
I32
32-bit integer
Float
32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source) the following combinations are possible when creating BICO
interconnections:
BICO input parameter
CI parameter
BI parameter
BICO output parameter U32/I16
U32/I32
U32/Float
U32/Bin
CO: U8
√
√
-
-
CO: U16
√
√
-
-
CO: U32
√
√
-
-
CO: I16
√
√
-
-
CO: I32
√
√
-
-
CO: Float
√
√
√
-
BO: U8
-
-
-
√
BO: U16
-
-
-
√
BO: U32
-
-
-
√
BO: I16
-
-
-
√
BO: I32
-
-
-
√
BO: Float
-
-
-
-
Legend:
√: BICO interconnection permitted
-: BICO interconnection not permitted