Parameter list
8.2 Parameter list
SINAMICS V20 Converter
204
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data set Data
type
Acc.
Level
r0052.0...15 CO/BO: Active status
word 1
-
-
-
-
-
U16 2
Displays first active status word of converter (bit format) and can be used to diagnose converter status.
Bit
Signal name
1 signal
0 signal
00
Converter ready
Yes
No
01
Converter ready to run
Yes
No
02
Converter running
Yes
No
03
Converter fault active
Yes
No
04
OFF2 active
No
Yes
05
OFF3 active
No
Yes
06
ON inhibit active
Yes
No
07
Converter warning active
Yes
No
08
Deviation setpoint/act. value
No
Yes
09
PZD control
Yes
No
10
|f_act| >= P1082 (f_max)
Yes
No
11
Warning: Motor current/torque limit
No
Yes
12
Brake open
Yes
No
13
Motor overload
No
Yes
14
Motor runs right
Yes
No
15
Converter overload
No
Yes
Dependency:
r0052 bit 03 "Converter fault active": Output of bit 3 (Fault) will be inverted on digital output (Low = Fault, High = No
Fault);
r0052 bit 06 "On inhibit" is active with OFF2 or OFF3 and becomes disabled with OFF1, NOT OFF2 and NOT OFF3.
Note:
See r2197 and r2198.
r0053.0...11 CO/BO: Active status
word 2
-
-
-
-
-
U16 2
Displays second status word of converter (in bit format).
Bit
Signal name
1 signal
0 signal
00
DC brake active
Yes
No
01
|f_act| > P2167 (f_off)
Yes
No
02
|f_act| > P1080 (f_min)
Yes
No
03
Act. current |r0068| >= P2170
Yes
No
04
|f_act| > P2155 (f_1)
Yes
No
05
|f_act| <= P2155 (f_1)
Yes
No
06
f_act >= setpoint (f_set)
Yes
No
07
Act. unfilt. Vdc < P2172
Yes
No
08
Act. unfilt. Vdc > P2172
Yes
No
09
Ramping finished
Yes
No
10
PID output r2294 == P2292 (PID_min)
Yes
No
11
PID output r2294 == P2291 (PID_max)
Yes
No
Notice:
r0053 bit 00 "DC brake active" ==> see P1233
Note:
See r2197 and r2198.