Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
229
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
r0730
Number of digital outputs -
-
-
-
-
U16 3
Displays number of digital outputs.
P0731[0...2]
BI: Function of digital
output 1
0 - 4294967295
52.3
U, T
-
CDS U32/
Bin
2
Defines source of digital output 1.
Notice:
An inverse logic can be realized by inverting the digital outputs in P0748.
Note:
Output of fault bit 52.3 is inverted on digital output. Therefore, with P0748 = 0, the digital output is set to
low when a fault is triggered, and when there is no fault, it is set to high.
Monitor functions ==> see r0052, r0053
Motor holding brake ==> see P1215
DC-Brake ==> see P1232, P1233
P0732[0...2]
BI: Function of digital
output 2
0 - 4294967295
52.7
U, T
-
CDS U32/
Bin
2
Defines source of digital output 2.
P0733[0...2]
BI: Function of digital
output 3
0 - 4294967295
0
U, T
-
CDS U32/
Bin
2
Defines source of digital output 3.
Note:
This digital output is provided by the optional I/O Extension Module.
P0734[0...2]
BI: Function of digital
output 4
0 - 4294967295
0
U, T
-
CDS U32/
Bin
2
Defines source of digital output 4.
Note:
This digital output is provided by the optional I/O Extension Module.
r0747.0...1
CO/BO: State of digital
outputs
-
-
-
-
-
U16 3
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Bit
Signal name
1 signal
0 signal
00
Digital output 1 energized
Yes
No
01
Digital output 2 energized
Yes
No
02
Digital output 3 energized
Yes
No
03
Digital output 4 energized
Yes
No
Dependency: Bit = 0 signal: Contacts open
Bit = 1 signal: Contacts closed
Note:
The digital output 3 and 4 are provided by the optional I/O Extension Module.
P0748
Invert digital outputs
-
0000 bin
U, T
-
-
U16 3
Defines high and low states of digital output for a given function.
Bit
Signal name
1 signal
0 signal
00
Invert digital output 1
Yes
No
01
Invert digital output 2
Yes
No
02
Invert digital output 3
Yes
No
03
Invert digital output 4
Yes
No
Note:
The digital output 3 and 4 are provided by the optional I/O Extension Module.
r0750
Number of analog inputs -
-
-
-
-
U16 3
Displays number of analog inputs available.