Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
267
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data set
Data
type
Acc.
Level
Note:
P1256 = 0:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage. The frequency is
kept above the frequency limit provided in P1257.
P1256 = 1:
Maintain DC-link voltage until mains is returned or converter is tripped with undervoltage or pulses are disa-
bled when frequency falls below the limit in P1257.
P1256 = 2:
This option ramps down the frequency to standstill even when mains return.
If mains do not return, frequency brought down under the control of Vdc_min controller until P1257 limit.
Then pulses are disabled or undervoltage has occurred. If mains return, then an OFF1 is active until P1257
limit. Then pulses are disabled.
P1257[0...2] Frequency limit for
kinetic buffering [Hz]
0.00 - 550.00
2.50
U, T
-
DDS
Float 3
Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256.
P1300[0...2] Control mode
0 - 19
0
C, T
-
DDS
U16 2
Parameter to select the control method. Controls relationship between speed of motor and voltage supplied
by converter.
0
V/f with linear characteristic
1
V/f with FCC
2
V/f with quadratic characteristic
3
V/f with programmable characteristic
4
V/f with linear eco
5
V/f for textile applications
6
V/f with FCC for textile applications
7
V/f with quadratic eco
19
V/f control with independent voltage setpoint