Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
275
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1810
Control word Vdc control 0 - 3
3
U, T
-
-
U16 3
Configures Vdc filtering and compensation.
Bit
Signal name
1 signal
0 signal
00
Enable Vdc average filter
Yes
No
01
Enable Vdc compensation
Yes
No
Note:
P1810 default for the single phase variants is 2.
P1820[0...2] Reverse output phase
sequence
0 - 1
0
T
-
DDS
U16 2
Changes sequence of phases without changing setpoint polarity.
0
Forward
1
Reverse the Motor
Note:
See P1000
P1825
On-state voltage of IGBT
[V]
0.0 - 20.0
0.9
U, T
-
-
Float 4
Corrects on-state voltage of the IGBTs.
P1828
Gating unit dead time
[μs]
0.00 - 3.98
0.01
U, T
-
-
Float 4
Sets compensation time of gating unit interlock.
P1829
Phase angle where out-
put frequency crossing
zero [°]
0.0 – 180.0
0.0
U, T
-
-
Float 4
Adjusts the phase angle at the point where the output frequency crosses zero. The angle is only used if
the output frequency changes direction.
P1900
Select motor data identi-
fication
0 - 2
0
C, T
-
-
U16 2
Performs motor data identification.
0
Disabled
2
Identification of all parameters in standstill
Dependency: No measurement if motor data incorrect.
P1900 = 2: Calculated value for stator resistance (see P0350) is overwritten.
Notice:
When the identification is finished P1900 is set to 0. When choosing the setting for measurement, observe
the following:
The value is actually adopted as P0350 parameter setting and applied to the control as well as being
shown in the read-only parameters below. Ensure that the motor holding brake is not active when per-
forming the motor identification.
Note:
Before selecting motor data identification, "Quick commissioning" has to be performed in advance.
Since the cable length of the applications differs in a wide range, the preset resistor P0352 is only a rough
estimation. Better results of the motor identification can be achieved by specifying the cable resistor be-
fore the start of the motor identification by measuring/calculating.
Once enabled (P1900 > 0), A541 generates a warning that the next ON command will initiate measure-
ment of motor parameters.
Communications - both via USS as well as via the Modbus - are interrupted for the time that it takes to