Parameter list
8.2 Parameter list
SINAMICS V20 Converter
312
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2802[0...13] Activate FFBs
0 - 3
0
U, T
-
-
U16 3
Enables free function blocks (FFB) and determines the chronological order of each function block. See P2801.
0
Not Active
1
Level 1
2
Level 2
3
Level 3
Index:
[0]
Enable timer 1
[1]
Enable timer 2
[2]
Enable timer 3
[3]
Enable timer 4
[4]
Enable ADD 1
[5]
Enable ADD 2
[6]
Enable SUB 1
[7]
Enable SUB 2
[8]
Enable MUL 1
[9]
Enable MUL 2
[10]
Enable DIV 1
[11]
Enable DIV 2
[12]
Enable CMP 1
[13]
Enable CMP 2
Dependency: Set P2800 to 1 to enable function blocks.
All active function blocks, enabled with P2802, will be calculated in every 128 ms.
P2803[0...2] Enable Fast FFBs
0 - 1
0
U, T
-
CDS
U16 3
Fast free function blocks (FFB) are enabled in two steps:
1.
P2803 enables the use of fast free function blocks (P2803 = 1).
2.
P2801 enables each fast free function block individually and determines the chronological order
(P2801[x] = 4 to 6).
0
Disable
1
Enable
Dependency: All active fast function blocks will be calculated in every 8 ms.
Note:
Attention: P2200 and P2803 are locked parameter against each other. PID and FFB of the same data set
cannot be active at same time.
P2810[0...1] BI: AND 1
0 - 4294967295
0
U, T
-
-
U32 3
P2810[0], P2810[1] define inputs of AND 1 element, output is r2811.
Index:
[0]
Binector input 0 (BI 0)
[1]
Binector input 1 (BI 1)
Dependency: P2801[0] assigns the AND element to the processing sequence.