Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P3950
Access of hidden pa-
rameters
0 - 255
0
U, T
-
-
U16
4
Accesses special parameters for development (expert only) and factory functionality (calibration parame-
ter).
r3954[0...12] CM info and GUI ID
-
-
-
-
-
U16
4
Used to classify firmware (only for SIEMENS internal purposes).
Index:
[0]
CM label (increment/branch)
[1]
CM label (counter)
[2]
CM label
[3...10]
GUI ID
[11]
GUI ID major release
[12]
GUI ID minor release
r3978
BICO counter
-
-
-
-
-
U32
4
Counts the number of changed BICO links.
P3981
Reset active fault
0 - 1
0
T
-
-
U16
4
Resets active faults when changed from 0 to 1.
0
No fault reset
1
Reset fault
Note:
See P0947 (last fault code)
Automatically reset to 0.
P3984
Client telegram off time
[ms]
100 - 10000
1000
T
-
-
U16
3
Defines time after which a fault will be generated (F73) if no telegram is received from the client.
Dependency: Setting 0 = watchdog disabled
r3986[0...1]
Number of parameters -
-
-
-
-
U16
4
Number of parameters on the converter.
Index:
[0]
Read only
[1]
Read & write
r4000 - r4064 Reserved