5.6.3.11
Running the converter in condensation protection mode
Functionality
If an external condensation sensor detects excessive condensation, the converter applies a
DC current to keep the motor warm to prevent condensation.
●
OFF1/OFF3: The condensation protection function is disabled when OFF3 is activated
and enabled again when OFF1 is activated.
●
OFF2/fault: The motor stops and the condensation protection is deactivated.
Setting parameters
Parameter
Function
Setting
P3852[0...2]
BI: Enable frost protection This parameter defines command source of protection enable command. If
binary input is equal to one, then protection will be initiated (factory default: 0).
I
f P3853 = 0 and P3854 ≠ 0,
condensation protection is applied by applying
the given current to the motor.
Note that the protection function may be overridden under the following cir-
cumstances:
•
If converter is running and protection signal becomes active, signal is
ignored
•
If converter is turning motor due to active protection signal and a RUN
command is received, RUN command overrides frost signal
•
Issuing an OFF command while protection is active will stop the motor
P3854[0...2]
Condensation protection
current [%]
This parameter specifies the DC current (as a percentage of nominal current)
which is applied to the motor when condensation protection is active.
Range: 0 to 250 (factory default: 100)