Installing and putting a SINAUT modem into operation
5.9 Installing and putting a SINAUT MD2, MD3, MD4 modem into operation
Station control system
272
System Manual, 07/2009, C79000-G8976-C178-07
5.9.4
Horizontal and vertical installation
Horizontal and vertical installation
A SINAUT modem can be operated both in a horizontal and in a vertical installation.
Permitted ambient temperature
The SINAUT modems can be operated in the same temperature range specified for the S7-
300.
Table 5- 49 Permitted ambient temperature for SINAUT modems
Installation position
Permitted ambient temperature
MDx
Horizontal
0 to 60 °C
MDx
Vertical
0 to 40 °C
Dimensions for installing SINAUT modems
Table 5- 50 Dimensions for installing SINAUT modems
Module
Module width
Module height
Max. depth
Modem module
MD2, MD3 and MD4
80 mm
125 mm
120 mm or 180 mm
with open front panel
5.9.5
Connecting to the power supply
WARNING
Connecting the modem module to a live power supply can damage the module. Connect
the modem to the power supply only when the power supply is off.