15188
[Channel %1: ] Error during execution of ASUB file %3.
Parameters:
%1 = Channel number
%2 = Is not used
%3 = ASUB file name
Explanation:
An error has occurred on executing an ASUB.
Alarm 15188 displays the name of the program that was started
as ASUB. Alarm 15188 is output together with the alarm that
describes the error cause. Alarm 15188 is also output when
the alarm occurs in a subroutine started from the ASUB.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Correct the ASUB file (subroutine).
Programm
continuation:
Clear alarm with the Delete key or NC START.
15189
[Channel %1: ] Error executing SAFE.SPF
Parameters:
%1 = Channel number
Explanation:
An error occurred while processing the NC initialization program for Safety Integrated /_N_CST_DIR/_N_SAFE_SPF. This
alarm is output together with the alarm describing the cause of the error.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Correct /_N_CST_DIR/_N_SAFE_SPF and perform an NCK reset.
Programm
continuation:
Switch control OFF - ON.
15190
[Channel %1: ] Block %2 not enough free memory for subroutine call
Parameters:
%1 = Channel number
%2 = Block number, label
Explanation:
The following deadlock has been found in the interpreter: Memory is needed for calling a subroutine. The module memory
is, however, empty and there is no prospect of module memory becoming free again by executing the preprocessing/main
run queue, because this queue is empty.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Increase machine data MD28010
$MC_MM_NUM_REORG_LUD_MODULES / MD28040 $MC_MM_LUD_VALUES_MEM / MD18210
$MN_MM_USER_MEM_DYNAMIC or program a preprocessing stop STOPRE before calling the subroutine.
Programm
continuation:
Clear alarm with NC START or RESET key and continue the program.
15300
[Channel %1: ] Block %2 invalid number-of-passed-blocks during block search
Parameters:
%1 = Channel number
%2 = Block number, label
Explanation:
In the function "Block search with calculation" a negative number of passes has been entered in column P (number of
passes). The permissible range of values is P 1 - P 9 999.
Reaction:
Alarm display.
Remedy:
Enter only positive number of passes within the range of values.
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
Diagnostics Manual
234
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2