400004
Code error: %2 network %1
Explanation:
%1 : Network number
%2 : Internal error code, module type
The user program contains an operation which is not supported by the control.
Type 1: Incorrect operand
Type 2: Incorrect operation
Type 3: Timer already used (TON or TONR)
Type 4: User program too large - memory overflow
Type 5: Excessive number of internal jump marks
Type 6: Excessive number of global jump marks
Type 7: Excessive number of SBRs
Type 8: Link error, unresolved references
Reaction:
PLC Stop
Remedy:
Modify and reload user program.
Programm
continuation:
Switch control OFF - ON.
400005
PLC stop specified from start-up menu
Explanation:
User program is not being processed
Reaction:
Alarm display.
Remedy:
Switch controller off/on
Programm
continuation:
Switch control OFF - ON.
400006
Loss of remanent PLC data
Explanation:
The following causes are possible:
Control handling (e.g. standard PLC deletion, power up with default values)
Control handling of power up with backed up data without backing up data in advance
Support time exceeded
Reaction:
Alarm display.
Remedy:
Update the data required.
Programm
continuation:
Clear alarm with the Delete key or NC START.
400007
Operand error: %3 %2 network %1
Explanation:
%1 : Network number
%2 : Block type, block number.
%3 : Variable address
Reaction:
PLC Stop
Remedy:
The variable displayed must be checked in the user program for violation of the address range, impermissible data type
and alignment errors.
Programm
continuation:
Switch control OFF - ON.
400008
Programming tool - version is not compatible %1 %2
Explanation:
%1 : Programming tool version
This version is not compatible with the product version of the control system.
Reaction:
PLC Stop
Remedy:
Translate the user program using a suitable programming tool version and load in the control.
SINUMERIK 808D ADVANCED alarms
5.5 PLC alarms
Diagnostics Manual
522
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2