400014
PROFINET - I/O ramp-up fault type: %1
Explanation:
%1: 1 PROFINET - I/O not ramped-up
2 Software version NC - PLC incompatibility
3 Number of slots per function exceeded
4 PROFINET I/O server not ready
Reaction:
PLC Stop
Remedy:
Type 1: Check PROFINET hardware and/or MD 11240
Types 2 to 3: Report error to Siemens
Type 4: 828D - Check and/or replace PCU hardware and/or check MD 11240
Programm
continuation:
Switch control OFF - ON.
400015
PROFINET - IO I/O fault: log. addr. %1 bus/station: %2
Explanation:
The PLC-UP is using I/O addresses which are not available.
%1 Logical I/O address
%2 Bus number/station number
Causes of error:
Bus peripheral has no voltage
Bus address set incorrectly
Bus connection faulty
Active MD 11240 (SDB configuration) is set incorrectly
Reaction:
PLC Stop
Remedy:
Rectify the error using the error cause
Programm
continuation:
Switch control OFF - ON.
400017
PLC TOOLMAN: missing table in DB9900
Explanation:
The PLC TOOLMAN cannot find one of the tables 9900, 9901 or 9902.
Reaction:
PLC Stop
Remedy:
Create the missing table(s).
Programm
continuation:
Switch control OFF - ON.
400018
PLC TOOLMAN: Spindle or load location invalid
Explanation:
The PLC TOOLMAN does not know the specified spindle or load location number.
Reaction:
PLC Stop
Remedy:
Specify the correct number.
Programm
continuation:
Switch control OFF - ON.
400019
PLC maintenance planner: Error in DB 9903 or 9904
Explanation:
PLC maintenance planner: DBs 9903 and 9904 must be present and must have the same length.
Reaction:
PLC Stop
Remedy:
Create block(s) correctly.
Programm
continuation:
Switch control OFF - ON.