Remedy:
Please inform the authorized personnel/service department.
Check and correct the identifier used in the MD10000 $MN_AXCONF_MACHAX_NAME_TAB, MD20080
$MC_AXCONF_CHANAX_NAME_TAB and/or MD20060 $MC_AXCONF_GEOAX_NAME_TAB.
Only with active "OEM transformation" compile cycle: In addition to the specified MD, check and correct MD24110
$MC_TRAFO_AXES_IN_1[n] of the activated OEM transformation according to the function description.
Programm
continuation:
Switch control OFF - ON.
4045
[Channel %1: ] Conflict between machine data %2 and machine data %3
Parameters:
%1 = Channel number
%2 = String: MD identifier
%3 = String: MD identifier
Explanation:
Using the specified machine data %1 leads to a conflict with machine data %2.
Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Correct the specified machine data.
Programm
continuation:
Switch control OFF - ON.
4050
NC code identifier %1 cannot be reconfigured to %2
Parameters:
%1 = String: Old identifier
%2 = String: New identifier
Explanation:
Renaming of an NC code was not possible for one of the following reasons:
- The old identifier does not exist
- The new identifier lies in another type range.
NC codes/keywords can be reconfigured via machine data as long as the type range is not abandoned.
Type 1: "real" G codes: G02, G17, G33, G64, ...
Type 2: named G codes: ASPLINE, BRISK, TRANS, ...
Type 3: settable addresses: X, Y, A1, A2, I, J, K, ALF, MEAS, ...
Type 1: "real" G codes: G02, G17, G33, G64, ...
Type 2: named G codes: CIP, TRANS, ...
Type 3: settable addresses: X, Y, I, J, K, MEAS
Reaction:
NC not ready.
Mode group not ready, also effective for single axes.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
Correct MD10712 $MN_NC_USER_CODE_CONF_NAME_TAB (protection level 1).
The list must be built up as follows:
Even address: Identifier to be modified.
Following odd address: New identifier
e.g.: $MN_NC_USER_CODE_CONF_NAME_TAB [10] = "ROT"
$MN_NC_USER_CODE_CONF_NAME_TAB [11] = " "
clears the ROT function from the control
Programm
continuation:
Switch control OFF - ON.