4060
Standard machine data loaded (%1, %2, %3, %4)
Parameters:
%1 = Identifier 1
%2 = Identifier 2
%3 = Identifier 3
%4 = Identifier 4
Explanation:
The standard MD were loaded because
- a cold start was requested or
- the MD buffer voltage failed or
- an initialization was requested for loading the standard machine data (MD11200 $MN_INIT_MD).
Power up with standard values through:
Operation (e.g. commissioning switch)
MD11200 $MN_INIT_MD
Loss of retentive data
Power up operation with data backup, without saving data before
Reaction:
Alarm display.
Remedy:
Please inform the authorized personnel/service department. After automatically loading the standard MDs, the individual
MDs must be entered or loaded in the relevant system.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
4062
Backup data loaded
Explanation:
The user data saved in the flash memory are loaded to the SRAM.
Reaction:
Alarm display.
Remedy:
Load specific machine data again.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
4065
Buffered memory was restored from backup medium (potential loss of data!)
Explanation:
The user data of the NC and the retentive data of the PLC are stored in a buffered memory area (SRAM). A possible
inconsistency was detected in this buffered memory during ramp-up of the control.
The buffered memory was initialized with the last backup copy. Changes that have been made since the last update of
the backup copy in the buffered memory were thus lost.
A possible reason for a data inconsistency could be that the backup time was exceeded. Please note the required ON
time of the control specified in your commissioning guide.
Reaction:
NC not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Restart the control.
Programm
continuation:
Switch control OFF - ON.
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
Diagnostics Manual
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2
57