Remedy:
General: The following must apply: 'maximum programmed address extension s (=spindle number/toolholder number)
of Ts=t, Ms=6 must be less than the value of MD18076 $MN_MM_NUM_LOCS_WITH_DISTANCE.
With magazine management: Check whether the toolholder number/spindle number and the magazine data have been
defined correctly.
(See also the system variables $TC_MPP1, $TC_MPP5 of the buffer magazine).
Programm
continuation:
Clear alarm with NC START or RESET key and continue the program.
6500
NC memory full
Explanation:
The NCK file system is full.
The available buffered memory does not suffice. Note: At first commissioning, files of the NC file system may be affected
such as drive data, MMC files, FIFO files, NC programs...
Reaction:
Alarm display.
Remedy:
Adjust the size of the buffered memory (MD18230 $MN_MM_USER_MEM_BUFFERED) or increase the space available
in the buffered memory, e.g. by unloading part programs that are no longer being used. Or decrease the size of the ring
buffer (see $MC_RESU_RING_BUFFER_SIZE).
Programm
continuation:
Clear alarm with the Delete key or NC START.
6510
Too many part programs in the NC memory
Explanation:
The maximum number of possible files in the NC file system (part of the NC memory) has been reached. Note: During first
commissioning, this can affect files from the NC file system, e.g. drive data, MMC files, FIFO files, NC programs, cycle
programs, ...
Reaction:
Alarm display.
Remedy:
Please inform the authorized personnel/service department.
- Delete or unload files (e.g. part programs), or
- Increase MD18320 $MN_MM_NUM_FILES_IN_FILESYSTEM or MD18321
MD_MAXNUM_SYSTEM_FILES_IN_FILESYSTEM.
- With the Siemens cycle storage, increase the number of files in the ressource file.
Programm
continuation:
Clear alarm with the Delete key or NC START.
6520
The value of the machine data %1%2 is too low
Parameters:
%1 = String: MD identifier
%2 = If required, index: MD array
Explanation:
The MD18370 $MN_MM_PROTOC_NUM_FILES specifies the number of protocol files for the protocol users. However,
more types are used than configured.
Reaction:
Alarm display.
Remedy:
Increase MD18370 $MN_MM_PROTOC_NUM_FILES.
Programm
continuation:
Clear alarm with the Delete key or NC START.
6530
Too many files in directory
Explanation:
The number of files in a directory of the NC memory has reached the maximum limit.
Reaction:
Alarm display.
Remedy:
Please inform the authorized personnel/service department.
- Delete or unload files (e.g. part programs) in the respective directory, or
- Increase MD18280 $MN_MM_NUM_FILES_PER_DIR.
Programm
continuation:
Clear alarm with the Delete key or NC START.
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
Diagnostics Manual
84
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2