PROFIBUS DP Communication
8.6 DP slave MCP 310
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
261
PROFIBUS parameters
As soon as you have inserted MCP 310 DP slave into the configuration, dialog box
"PROFIBUS properties interface SINUMERIK MCP" is displayed.
The following PROFIBUS parameters must either be set or verified:
●
PROFIBUS address
●
Transmission rate
●
Profile
Dialog
Dialog: Properties - PROFIBUS interface SINUMERIK MCP
Tab: Parameter
address: <PROFIBUS address>
Button: "Properties..."
Dialog: PROFIBUS properties
Tab: Network settings
Data transfer rate: 12 Mbps
Profile: DP
OK
OK
NOTICE
The PROFIBUS address set in the S7 project for the MCP 310 DP slave must be the same
as the PROFIBUS address (DIP Switch S3) set in the module.
There is no automatic adjustment!
The following data must agree:
1.
SIMATIC configuration of MCP 310 DP slave
PROFIBUS address
2.
Machine control panel MCP 310
PROFIBUS address (DIP Switch S3)