PROFIBUS DP Communication
8.7 DP slave MCP 483
Manual
278
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
Insert module
The active functions and hence the number of user data elements to be transferred are
chosen by selecting the appropriate pre-configured module. The modules in the hardware
catalog are arranged under the MCP 483 DP slave. The following modules are available:
●
Universal module (not applicable)
●
standard
●
standard, handwheel
●
standard, extended
●
standard, handwheel, extended
Module: standard
The module transfers the data for the "Standard" function:
●
Input data: 8 bytes
6WDQGDUGGDWD
E\WHV
●
Output data: 8 bytes
6WDQGDUGGDWD
E\WHV
Module: standard, handwheel
The module transfers the data for the "Standard" and "Handwheel" functions:
●
Input data: 12 bytes
+LJK%\WH
/RZ%\WH
&XVWRPHU/('
E\WH
5HVHUYHG
E\WH
6WDQGDUGGDWD
E\WHV
●
Output data: 8 bytes
6WDQGDUGGDWD
E\WHV