NC Commissioning with HMI Advanced
11.8 Loadable compile cycles
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
479
11.8.1
Load a compile cycle
Requirement
To transfer the compile cycle to the control, the following requirements must be met:
●
There is a network connection (TCP/IP) between the PCU and an external computer
(PC/PG) on which the compile cycle is located.
●
Storage media can be connected to the PCU (e.g. USB FlashDrive) on which the compile
cycle is saved.
Implementation
Perform the following operation to load one or more compile cycles into the NC:
1.
End the active SINUMERIK user interface (e.g. HMI Advanced) and activate the
SINUMERIK desktop (see Chapter "Activation" (Page 135)).
2.
Use Windows Explorer to copy the compile cycle file (e.g. ccresu.elf) from the external
computer (PC/PG) or the CD/disk drive to the following directory on the PCU:
F:\card\oem\sinumerik\oa\
3.
Trigger an NC reset to load the compile cycles into the NC system software.
11.8.2
Interface version compatibility
A SINUMERIK-specific interface is used for communication between the compile cycle and
NC system software. Therefore, the interface version of a loaded compile cycle must be
compatible with the interface version of the NC system software. Each interface version is
displayed under:
●
Interface version of the NC system software
HMI Advanced:
Diagnosis > Service Display > Version > NCU Version
Display (excerpt)