NC Commissioning with HMI Advanced
11.10 Initial settings
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
485
11.10
Initial settings
Concept
The status of an NC function, e.g. G codes, tool length offset, transformation, coupled motion,
etc., which is taken in a certain status of a channel is a default setting.
Channel states for which default settings can be parameterized are:
1.
Power up (NC reset), reset (channel or mode group reset) and end of part program
and
2.
Part program start
The default setting of an NC function is stored until it is explicitly changed by operation or
programming.
Parameterize initial settings
The relevant initial settings are parameterized via the following machine data:
●
MD20110 $MC_RESET_MODE_MASK ("Definition of the control default settings in case
of reset")
●
MD20112 $MC_START_MODE_MASK (Definition of the control default settings in case
of NC start)
●
MD20150 $MC_GCODE_RESET_VALUES ("Delete position of the G codes")
●
MD20152 $MC_GCODE_RESET_MODE ("G code default setting in case of reset")
Table 11-57 Default settings that can be parameterized through MD
Status
can be parameterized via MD
Power up (POWER ON)
MD20110 $MC_RESET_MODE_MASK
MD20150 $MC_GCODE_RESET_VALUES
RESET/part program end
MD20110 $MC_RESET_MODE_MASK
MD20150 $MC_GCODE_RESET_VALUES
MD20152 $MC_GCODE_RESET_MODE
Part program start
MD20112 $MC_START_MODE_MASK
MD20110 $MC_RESET_MODE_MASK
References:
/FB1/ Function Manual - Basic Functions; K2 Axes, Coordinate Systems, Frames, Workpiece
numbers IWS Chapter: "Workpiecerelated actual value system/reset response"