Drive commissioning (SINAMICS)
9.2 ONLINE commissioning
Manual
326
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
9.2.10
Control Unit: Output "Infeed operation" (BICO interconnection) signal
To output the "Infeed operation" signal at terminal X132.7 of the Control Unit, parameter:
"r863 Bit 0" of the infeed must be connected to parameter: "p742" of the Control Unit via
BICO interconnection:
●
Infeed: r863 Bit 0: BI: Infeed operation
●
Control Unit: p742, BI: CU signal source for terminal DI/DO 12
and terminal X132.7 of the Control Unit must then be parameterized as output DO12.
Implementation
Perform the following actions:
1.
To open the terminal configuration in the project navigator double-click on. Project > Drive
unit_Adr10 > Control Unit > Inputs/outputs.
2.
In the "Bidirectional digital inputs/outputs" tab (1), change the status for terminal X132.7
to "Output" (2)
3.
Click the binector input icon of terminal X132.7, DO12 (3) and select the signal: Infeed
"r863: Bit0, ... Infeed operation" (4).
;
U%LW&2%2'ULYHFRXSOLQJVWDWXVFRQWUROZRUG&RQWUROOLQHFRQWDFWRU <HV 1R
U%LW&2%2'ULYHFRXSOLQJVWDWXVFRQWUROZRUG,QIHHGRSHUDWLRQ <HV 1R
U%LW%20DVWHUFRQWURODFWLYH0DVWHUFRQWURODFWLYH <HV 1R
)XUWKHULQWHUFRQQHFWLRQV
,QIHHG
'ULYHB
'ULYHB
'ULYHB
&RQWUROB8QLW
'2
,QSXW
0HDVXULQJVRFNHWV
%LGLUHFWLRQDOGLJLWDOLQSXWVRXWSXWV
&RQWUROB8QLW
'2
+HOS
,QIHHG
2XWSXW
'LJLWDOLQSXWV
,QYHUWRXWSXW