User data backup/Series commissioning
15.4 Importing a series startup file with HMI Advanced
Manual
548
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
NOTICE
The creation of a series-commissioning file with PLC data while the PLC is in RUN status
(cyclic operation) may result in an inconsistent PLC image in the series commissioning
archive.
After this series startup file has been copied back, this data inconsistency in the PLC user
program may under certain circumstances result in the stop of the PLC.
Changing the PLC operating status
To change the PLC operating status, proceed as follows:
●
With 840Di startup:
–
Start 840Di startup via the Windows taskbar > Start > Programs > SINUMERIK 840Di
> 840Di Startup.
–
Open the dialog box: Menu command Window > Diagnosis > NC/PLC.
●
With HMI Advanced
–
Open the dialog box: Operating area switchover > Start up > NC/PLC Diagnosis
●
Change the PLC operating state: PLC group buttons:"STOP"and "RUN".
●
NCK and PLC must then be resynchronized: PLC group buttons: "NC Reset".
15.4
Importing a series startup file with HMI Advanced
The process of reading in a series startup file is broken down into the following steps:
1.
Open the menu to read in a series startup file:
Operating range switchover > Services > Key ">" > Series startup > Import startup
archive
2.
Select the series startup file
3.
Start read in: START
Note
Because of the file extension ".arc" of the series startup file, this is also called archive.