06.03
7.3 SIMATIC S7 project
7-236
Siemens AG, 2003. All rights reserved
SINUMERIK 840Di Manual (HBI) – 06.03 Edition
S
Because DP slaves 611U can be assigned both to the NC and to the PLC,
check system functions SFC 14 and SFC 15 when writing data to see
whether the drive belongs to the writing component. If this is not the case,
the data access is denied.
The overview example shows the interrelations or interdependencies when con-
figuring the PROFIBUS DP communication between the components:
S
NC
S
DP master
S
DP Slave 611U
NC
I/O address, message frame type
MD13050: DRIVE_LOGIC_ADDRESS[ n ]
1. machine axis: 272
2. machine axis: 292
Check MD 13060: DRIVE_TELE-
GRAM_TYP[ n ]
1. machine axis: 102
2. machine axis: 102
DP master
PROFIBUS address, slot and I/O address
(message frame type)
PROFIBUS address: 10
Axis 1: Slot 5/6, I/O addr. 272
Axis 2: Slot 9/10, I/O addr. 292
(Message frame type: 102)
DP save 611U
PROFIBUS address, message frame type
PROFIBUS address: 10
Message frame type: 102
Axis 1 / Drive A
Axis 2 / Drive B
Header
Trailer
PIV/PDA
Axis 1/
drive A
PROFIBUS DP
Cyclic message frame: 102
1
2
PIV/PDA
Axis 2/
drive B
3
Fig. 7-8
Dependencies: NC, PLC/DP master and DP slave (SIMODRIVE 611 universal)
Dependencies:
PROFIBUS DP
communication
7 PROFIBUS DP Communication