06.03
9.1 SIMODRIVE 611 universal/E, POSMO CD/CA and SI
9-265
Siemens AG, 2003. All rights reserved
SINUMERIK 840Di Manual (HBI) – 06.03 Edition
9.1.2
Preconditions for an online connection
In order to be able to establish an online connection between SimoCom U and
the SIMODRIVE 611 universal drives connected using PROFIBUS DP, the fol-
lowing preconditions must be fulfilled:
S
SimoCom U must be installed
–
For installing SimoCom U, see Section 9.2, page 9-271
S
A PROFIBUS connection must exist from the PROFIBUS interface of the
MCI board to all drives
–
For network rules, see Section 7.2, page 7-210
S
With all drives, the PROFIBUS address must be set
–
For SIMODRIVE 611 universal/E see Subsection 9.1.3, page 9-265
–
For SIMODRIVE POSMO CD/CA and SI see Subsection 9.1.4, page
9-267
S
The SINUMERIK 840Di PLC must be networked using MPI
–
For networking the PLC, see Subsection 7.3.2, page 7-212
S
The configuration must be loaded into the PLC
–
For creating an S7 project, see Section 7.3, page 7-211
–
For loading the PLC, see Subsection 7.3.8, page 7-238
S
The MPI interface must be set on the “SINUMERIK MCI Card (MPI)”
–
For setting the MPI interface, see Subsection 9.1.5, page 9-268
S
The routing information must be set
–
For setting the routing Information, see Subsection 9.1.6, page 9-269.
9.1.3
Setting a PROFIBUS address (SIMODRIVE 611 universal/E)
For SimoCom U to be able to enter online operation with the SIMODRIVE drives
connected to the PROFIBUS, the PROFIBUS address specified in the S7 proj-
ect (see Section 7.3, page 7-211f) must be set on DP slave 611U or UE in ques-
tion using the display and operator unit.
+
P
–
Control unit
Display
Fig. 9-1
Display and control unit
9 Drive Start-Up (Preconditions)