SIPART DR19
80
C73000-B7474-C140-06
Configuring
Quick Reference
3.7
AdAP - End-Adaptation
During adaptation the signal lamp ADAPT (16) flashes. The duration of the adap-
tation depends on the delay in the process.
You can switch from automatic to manual mode or from manual to automatic mode
during adaptation - press button
(9) once.
The adaptation process can be ended in the following ways:
•
Adaptation ended error-free (automatic);
•
Adaptation is aborted manually;
•
Adaptation is aborted automatically
If adaptation is ended in automatic mode:
If adaptation is ended in manual mode:
By pressing the exit button (13)
By error monitoring:
Signal lamp AdAPT (16):
off
Operation and monitoring front:
process control level
Controller operating mode:
automatic mode,
the controller operates according to
the new control parameters.
Signal lamp AdAPT (16):
off
Operation and monitoring front:
process control level
Controller operating mode:
manual mode,
the output manipulated value y
causes as small a control difference
as possible
After switching to automatic mode, the controller operates according to the new
control parameters.
Signal lamp AdAPT (16):
off
Operation and monitoring front:
process control level
Controller operating mode:
manual mode (YS is output)
The original control parameters are retained.
Signal lamp AdAPT (16):
off
Operation and monitoring front:
selection level l
Controller operating mode:
manual mode (YS is output)
Adaptation
process
End of
adaptation
Adaptation
is ended
without
error
Adaptation
is aborted
manually