SIPART DR20
Project Planning Manual
Planning example
K8
Fixed setpoint control, controlled variable direct from a
thermocouple (internal cold junction), setpoint w adjusted
remotely (resistance transmitter)
W
x
y
Drive
The controlled variable x from the thermocouple is applied to
the analog input AE3. The measuring range is
programmable. The controlled variable must be linearized
(see instructions on pages 78 and 91).
The manipulated variable output is 0 to 20 mA; it can be
reconfigured to 4 to 20 mA (S37 = 1).
The alarm circuit monitors the negative deviation Xd for max.
/ min. deviations (set parameters A2 = min. and A1 = max. !).
PIease refer to the remarks on page 108 !
Setting of configuring switches: S1 = 4, S8 = 1, S10 = 1, S14 = 1
AE1
AE2
BE
BA
L+
GND GND
Iy
1
2
3
4
5
6
7
8
SIPART DR20 K
6DR2004-1 (AC 230 V)
6DR2004-2 (AC 115 V)
6DR2004-4
(UC 24 V)
1
2
3
4
1
2
3
4
1
2
3
4
PE
N
L
AC 115 V
AC 230 V
⎫
⎬
⎭
PE
N
UC 24 V
L
⎫
⎬
⎭
Slot 3 GW
Slot 2 AE4
Slot 1 AE3
5
M1
A1
R1
A2
M2
Option module
6DR2801-8A
M
M/A
S
E
I
y
+
-
+
-
R
comp
X
Option module
6DR2800-8T
Option module
6DR2800-8R
-
+
R
A
R
E
S
Remote setpoint W
EA
R = R
A
+
∆
R + R
E
119