Project Planning Manual
SIPART DR20
The variable applied to input x1 is indicated as the actual value x. The limit monitors A1/A2 can be
configured to the mentioned variables.
The two-digit display can also indicate a further process variable in %. The associated input signal
is yR / yN.
The station provides further facilities in this mode:
−
If the basic device is a K controller, the variable displayed on the four-digit display as setpoint
w is output as a current signal of 0 or 4 to 20 mA via the analogue output. It is a setpoint
transmitter with local/remote switchover in addition.
−
If the basic device is an S controller,
the signals of a second alarm monitor can be output via
the
±
∆
Y outputs. The switching thresholds of this alarm monitor are set by parameters ya
(min.) and ye (max.) with a hysteresis of 1 %. The associated input signal is yR / yN.