5 Operation
5.4 Configuration modes
Manual
SIPART DR21
C73000-B7476-C143-08
167
Structure
switch
switch
posi-
tion
Function
S9
Thermocouple type AI3 (slot 1) with UNI--module (only active at S8=1/2)
[0]
Type L
1
Type J
2
Type K
3
Type S
4
Type B
5
Type R
6
Type E
7
Type N
8
Type T
9
Type U
10
any type (without linearization)
s
S10
Temperature unit AI3 (slot 1) with UNI--module (only active at S8=1/2/3/4/5)
put
s
[0]
Degrees Celsius
inp
u
1
Degrees Fahrenheit
log
in
2
Kelvin
A
nal
o
S11
S12
S13
S14
Root extraction AI1 to AI4
no
yes
AI1
[0]
1
AI2
[0]
1
AI3
[0]
1
AI4
[0]
1
S15
S16
S17
S18
S19
S20
Assignment of x1, x2, x3, yN, yR, z from AI1A to AI4A
0 %
AI1A
AI2A
AI3A
AI4A
x1
0
[1]
2
3
4
x2
0
1
[2]
3
4
x3/we
0
1
2
[3]
4
y
N
0
1
2
3
[4]
y
R
[0]
1
2
3
4
z
[0]
1
2
3
4
S21
Assignment of the linearizer (see ofPA) open
[0]
none
ut
s
1
AI1
inp
u
2
AI2
alog
in
3
AI3
An
a
4
AI4
A
5
x1
S22
Assignment slot 3
[0]
not used
3
1
4 DO / 2 DI
(DO3 -- DO6 / DI3, DI4)
4 DO / 1 DI
(DO3 -- DO6 / DI3, DI4=0)
S
lot
3
2
5 DI
(DI3 -- DI7)
Sl
3
2 relays
(DO3, DO4)
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...