SIPART PS2 (6DR5...)
50
A5E03436620-AB, 01/2017
Without Ex protection
With Ex protection Ex "ia" With Ex protection Ex "ic",
"ec", "t", "nA"
•
Auxiliary power U
H
U
H
≤ DC
35 V
I
≤
20 mA
-
-
•
Connecting to circuits with the
following peak values
-
U
i
= DC 15 V
I
i
= 25 mA
P
i
= 64 mW
"ic":
U
i
= DC 15 V
I
i
= 25 mA
"ec"/"nA":
U
n
≤
DC 15 V
P
n
≤
64 mW
Effective internal capacitance
-
C
i
= 5.2 nF
C
i
= 5.2 nF
Effective internal inductance
-
L
i
= negligibly small
L
i
= negligibly small
Galvanic isolation
The 3 outputs are galvanically isolated from the basic device.
Test voltage
DC 840 V, 1 s
7.5.4
Mechanical limit switch module
Without Ex protection
With Ex protection Ex ia
With Ex protection Ex "ic",
"t"
Mechanical limit switch module
6DR4004-8K
6DR4004-6K
6DR4004-6K
Limit encoder with mechanical
switching contacts
2 limit contacts
•
Binary output 1: Terminals 41 and
42
•
Binary output 2: Terminals 51 and
52
•
Max. switching current AC/DC
4 A
-
-
•
For connecting to circuits with the
following peak values
-
U
i
= 30 V
I
i
= 100 mA
P
i
= 750 mW
"ic":
U
i
= 30 V
I
i
= 100 mA
"t":
U
n
= 30 V
I
n
= 100 mA
Effective internal capacitance
-
C
i
= negligibly small
C
i
= negligibly small
Effective internal inductance
-
L
i
= negligibly small
L
i
= negligibly small
•
Max. switching voltage AC/DC
250 V/24 V
DC 30 V
DC 30 V
1 fault message output
•
Binary output: Terminals 31 and
32
•
Connection
On switching amplifier according to EN 60947-5-6: (NAMUR), UH = 8.2 V, Ri =
1 k
Ω).
•
Signal state High
(not triggered)
R = 1.1
kΩ
> 2.1 mA
> 2.1 mA
•
Signal state Low (triggered)
R = 10
kΩ
< 1.2 mA
< 1.2 mA
•
Auxiliary power
U
H
≤ DC
35 V
I
≤
20 mA
-
-
•
Connecting to circuits with the
following peak values
-
U
i
= 15 V
I
i
= 25 mA
P
i
= 64 mW
"ic" :
U
i
= 15 V
I
i
= 25 mA
"t":
U
n
= 15 V
I
n
= 25 mA