SIPART PS2 (6DR5...)
52
A5E03436620-AB, 01/2017
Additional modules
Without Ex protection
With Ex protection
Ex "ia"
With Ex protection
Ex "ic", "ec", "nA"
Hysteresis
± 0.2 %
Temperature influence (range:
rotation angle 120° or stroke 14 mm)
≤
0.1 %/10
K (≤
0.1 %/18 °F) for -20 to +90 °C (-4 to +194 °F)
≤
0.2%/10
K (≤
0.2%/18 °F) for -40 to -20 °C (-40 to -4 °F)
Climate class
According to IEC/EN 60721-3
•
Storage
1K5, but -40 to +90 °C (-40 to +194 °F)
•
Transport
2K4, but -40 to +90 °C (-40 to +194 °F)
Vibration resistance
•
Harmonic oscillations
(sine) according to IEC 60068-2-6
3.5 mm (0.14"), 2 to 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axis
•
Bumping according to IEC 60068-
2-29
300 m/s
2
(984 ft/s
2
), 6 ms, 4000 shocks/axis
Torque for cable gland nut made of
Plastic
Metal
Stainless steel
2.5 Nm (1.8 ft lb)
4.2 Nm (3.1 ft lb)
4.2 Nm (3.1 ft lb)
Housing protection type
IP68 according to IEC/EN 60529; NEMA 4X / Encl. Type 4X
For connecting to circuits with the
following peak values
-
U
i
= 5 V
I
i
= 160 mA
P
i
= 120 mW
U
i
= 5 V
Effective internal capacitance
-
C
i
= 180 nF
C
i
= 180 nF
Effective internal inductance
-
L
i
= 922
μH
L
i
= 922
μH
Certificates and approvals
CE conformity
The applicable directives and applied standards with their revision levels can be
found in the EU declaration of conformity on the Internet.
Explosion protection
Types of protection
Ex markings
ATEX/IECEx
FM/CSA
•
Intrinsic safety "ia"
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
IS, Class I, Divison 1, ABCD
IS, Class I, Zone 1, AEx ib, IIC
•
Intrinsic safety "ic"
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
-
•
Increased safety "ec" / non-
sparking "nA"
Zone 2:
II 3 G Ex ec IIC T6/T4 Gc
NI, Class I, Divison 2, ABCD
NI, Class I, Zone 2, AEx ec, IIC
Permissible ambient temperature
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
T4: -40 ... +85 °C (-40 ... +185 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
7.5.7.2
External position detection system C73451-A430-D78 and 6DR4004-1ES
Ambient temperature
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
•
Perm. ambient temperature for operation
-40 ... +90 °C (-40 ... +194 °F)
Degree of protection
1)
IP66 to IEC/EN 60529 / NEMA 4X
Climate class
According to IEC/EN 60721-3
•
Storage
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
•
Transport
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
•
Operation
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
1
) Impact energy max. 1 joule.
Summary of Contents for SIPART PS2 6DR5 series
Page 1: ......
Page 2: ......
Page 3: ...1 English 3 Français 59 Deutsch 118 Español 176 Italiano 236 Nederlands 295 ...
Page 4: ......
Page 356: ......