Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
142
Operating Instructions, 09/2007, A5E00127926-07
Parameter
Function
Parameter values
Unit
L4.FACT3
Factor 3
0.1 ... 5.0... 40.0
Overview parameter O
Parameter
Function
Parameter values
Unit
O. DCHG
Monitoring the changes in direction with the following parameters:
O1.LIMIT
Limit for the number of changes of direction
1 ... 1E6 ... 1E8
O2.FACT1
Factor 1
0.1 ... 1.0 ... 40.0
O3.FACT2
Factor 2
0.1 ... 2.0 ... 40.0
O4.FACT3
Factor 3
0.1 ... 5.0... 40.0
Overview parameter P
Parameter
Function
Parameter values
Unit
P. PAVG
Position mean value calculation with the following parameters:
P1.TBASE
Time base of the mean value generation
0.5h / 8h / 5d / 60d / 2.5y
P2.STATE
State of the position mean value calculation
IdLE / rEF / ###.# / Strt
P3.LEVEL1 Threshold 1
0.1 ... 2.0 ... 100.0
%
P4.LEVEL2 Threshold 2
0.1 ... 5.0 ... 100.0
%
P5.LEVEL3 Threshold 3
0.1 ... 10.0 ... 100.0
%
10.2
Description of parameters
10.2.1
Description of parameters 1 to 5
1.YFCT - actuator type
You can use this parameter to adjust the positioner as per the respective actuator and, if
required, as per the position sensor used. The following parameter values are available:
●
YFCT = turn
Use this parameter value for a part-turn actuator.
If you select "turn", the following parameter "2.YAGL" is automatically set to 90° and
cannot be changed.
●
YFCT = WAY (factory setting)
Use this parameter value for a linear actuator. The positioner compensates the non-
linearity caused due to the transformation of the linear movement of the linear actuator
into the rotary movement of the feedback shaft. For this purpose, the positioner is set in