Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
208
Operating Instructions, 09/2007, A5E00127926-07
Byte
Bit Name and meaning
Cause
Measure
Group
7
IDENT_NUMBER_VIOLATION
Identification number changed
To determine the cause, check
in DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
Modify the
configuration data
(change the GSD)
such that it is
consistent with the
identification
number set in the
device.
-
0
DIA_MAINTENANCE_ALARM
Maintenance alarm
To determine the cause, check
in DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
Depends on the
triggering
diagnostics event.
M
1
DIA_MAINTENANCE_DEMANDED
Maintenance demand
To determine the cause, check
in DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
Depends on the
triggering
diagnostics event.
M12, M
2
DIA_FUNCTION_CHECK
Functional check
The device is in the on-site
operation or
FEEDBACK_VALUE is
simulated
-
F
3
DIA_INV_PRO_COND
Invalid process conditions
To determine the cause, check
in DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
Depends on the
triggering
diagnostics event.
P
2
4
... 7
Reserved
-
-
-
0
... 6
Reserved
-
-
-
3
7
EXTENSION_AVAILABLE
Extension available
Further information about the
triggering diagnostics event is
available in
DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2.
-
-