Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
211
11.3.4.6
List of diagnostics events with status and diagnostics message for deactivated condensed
status
A list of diagnostics events with status and diagnostics message for deactivated condensed
status is given in the following table. DIAGNOSTICS_EXTENSION and
DIAGNOSTICS_EXTENSION_2 are physical block parameters.
DIAGNOSTICS_EXTENSION physical block parameter
Hard-coded effect of a diagnostics event
Byte Bit
No.
Diagnostics events
Quality status code
DIAGNOSTICS bit
0
1
Run time error of the actuator Bad, maintenance requirement DIA_SUPPLY
1
2
The device is not in the
"Automatic mode"
Uncertain, simulation value
None
2
3
Binary 1 is active (only
message)
Good, maintenance required
DIA_MAINTENANCE
3
4
Action triggered by binary
input 1
Uncertain, simulation value
None
4
5
Binary 2 is active (only
message)
Good, maintenance required
DIA_MAINTENANCE
5
6
Action triggered by binary
input 2
Uncertain, simulation value
None
0
7 ... 21 Reserved
-
-
5
22
Limit for alarm A1 exceeded
Good, maintenance required
DIA_MAINTENANCE
6
23
Limit for alarm A2 exceeded
Good, maintenance required
DIA_MAINTENANCE
2
7
24
Error in the device electronic
unit
Bad, device error
DIA_MEM_CHKSUM
0
25
The device is not yet ready for
operation (not initialized)
Bad, configuration error
DIA_NOT_INIT
1
26
The device is not yet ready for
operation (initialization error)
Bad, configuration error
DIA_INIT_ERR
3
27
Reserved
-
-
3
28
Reserved
-
-
4
29
Device in the Manual mode
(FB in the Manual mode)
Depends on the set status
None
5
30
Device in the Simulation mode
(FEEDBACK is simulated)
Depends on the simulated
status
None
6
31
Device in the TRACE mode
-
None
7
32
Diagnostics simulation
(diagnostics events are
simulated)
Depends on the simulated
diagnostics event
Depends on the simulated
diagnostics event
3
33 ... 48 Reserved
-
-