Alarm, fault and system messages
12.2 Diagnostics
SIPART PS2 with PROFIBUS communication
224
Operating Instructions, 09/2007, A5E00127926-07
No.
Abbreviation Meaning
Values that can
be displayed
Unit
Reset
possibl
e
10
LEAK
Leakage (Leakage)
P 0.0 ... 100.0
%
-
11
PST
Monitoring of the partial stroke test
OFF / ###.#, fdini,
notSt, SdtSt,
fdtSt, notd, Strt
s for ###.#
-
12
PRPST
Time since the last Partial-Stroke-Test
###, notSt, Sdtst,
fdtSt
Days
-
13
NXPST
Time until the next Partial-Stroke-Test
###, notSt, SdtSt,
fdtSt
Days
-
14
DEVI
General control valve fault
OFF, 0.0 ... 100.0 %
-
15
ONLK
Pneumatic leakage
OFF, 0.0 ... 100.0 -
-
16
STIC
Static friction/Slipstick effect
OFF, 0.0 ... 100.0 %
-
17
ZERO
Zero point displacement
OFF, 0.0 .. 100.0 %
-
18
OPEN
Displacement of upper end stop
OFF, 0.0 ... 100.0 %
-
19
PAVG
Position average
0.0 ... 100.0
%
-
20
P0
Potentiometer value of lower end stop (0%)
0.0 ... 100.0
%
-
21
P100
Potentiometer value of upper end stop (100%)
0.0 ... 100.0
%
-
22
IMPUP
lmpulse length up (Impuls Length Up)
2 ... 160
ms
-
23
IMPDN
Impulse length down (Impuls Length Down)
2 ... 160
ms
-
24
DBUP
Dead zone up (Dead Band Up)
0.1 ... 10.0
%
-
25
DBDN
Dead zone down (Dead Band Down)
0.1 ... 10.0
%
-
26
SSUP
Slow step zone up (Short Step Zone Up)
0.1 ... 100.0
%
-
27
SSDN
Slow step zone down (Short Step Zone Down)
0.1 ... 100.0
%
-
28
TEMP
Current temperature
-40 ... 85
°C
-
29
TMIN
Minimum temperature ("min/max pointer")
-40 ... 85
°C
-
30
TMAX
Maximum temperature ("min/max pointer")
-40 ... 85
°C
-
31
T1
Number of operating hours in temperature range 1
0 ... 4.29E9
Hours
-
32
T2
Number of operating hours in temperature range 2
0 ... 4.29E9
Hours
-
33
T3
Number of operating hours in temperature range 3
0 ... 4.29E9
Hours
-
34
T4
Number of operating hours in temperature range 4
0 ... 4.29E9
Hours
-
35
T5
Number of operating hours in temperature range 5
0 ... 4.29E9
Hours
-
36
T6
Number of operating hours in temperature range 6
0 ... 4.29E9
Hours
-
37
T7
Number of operating hours in temperature range 7
0 ... 4.29E9
Hours
-
38
T8
Number of operating hours in temperature range 8
0 ... 4.29E9
Hours
-
39
T9
Number of operating hours in temperature range 9
0 ... 4.29E9
Hours
-
40
VENT1
Number of switching cycles of pilot valve 1
0 ... 4.29E9
-
-
41
VENT2
Number of switching cycles of pilot valve 2
0 ... 4.29E9
-
-
42
STORE
Save the current value as "last maintenance" (press
the increment button for 5 s) (Store)
-
-
-
43
PRUP
Prediction up
1 ... 40
-
-
44
PRDN
Prediction down
1 ... 40
-
-
45
WT00
Number of operating hours in the actuating range
WT00
0 ... 4.29E9
Hours
X