Technical data
14.2 Technical data of SIPART PS2 PA
SIPART PS2 with PROFIBUS communication
246
Operating Instructions, 09/2007, A5E00127926-07
14.2
Technical data of SIPART PS2 PA
Standard controller
without explosion
protection
Standard controller
with EEx d explosion
protection
(flameproof
enclosure)
Standard controller
with EEx ia/ib
explosion protection
Standard controller
with EEx n
explosion protection
Explosion protection as per EN
50014, EN 50020 and
EN 50021
Without
EEx d
II 2 G EEx d II C
T4/T5/T6
EEx ia/ib
II 2 G EEx ia/ib II C
T6
EEx n
II 3 G EEx nA L [L]
II C T6/T5/T4 X
Installation point
Zone 1
Zone 1
Zone 2
Permissible ambient
temperature for operation
Restricted display refresh rate
of the LCD at 10°C (+14°F).
(For standard controllers with
explosion protection: only T4 is
permitted when using with the
I
y
module)
-30 ... +80°C
(-22 ... +176°F)
T4: -30 ... +80°C (-22 ... +176°F)
T5: -30 ... +65°C (-22 ... +149°F)
T6: -30 ... +50°C (-22 ... +122°F)
T4: -20 ... +75°C
T5: -20 ... +65°C
T6: -20 ... +50°C
Electrical data
Standard controller
without explosion
protection
Standard controller
with EEx d explosion
protection
(flameproof
enclosure)
Standard controller
with EEx ia/ib
explosion protection
Standard controller
with EEx n explosion
protection
Input
Auxiliary power supply
(terminals 6/7)
Bus-powered
Bus-powered
Bus-powered
Bus-powered
Bus voltage
9 ... 32 V
9 ... 32 V
9 ... 24 V
9 ... 32 V
•
Bus connection with a
FISCO supply unit, ia or ib
group IIC or IIB
Max. supply voltage U
o
-
-
17.5 V
-
Max. short circuit current
I
o
-
-
380 mA
-
Max. power P
o
-
-
5.32 W
-
•
Bus connection with a
barrier, ia or ib group IIC or
IIB
Max. supply voltage U
o
-
-
24 V
-
Max. short circuit current
I
o
-
-
250 mA
-
Max. power P
o
-
-
1,2 W
-
Current consumption
10.5 mA ± 10%
10.5 mA ± 10%
10.5 mA ± 10%
10.5 mA ± 10%