Configuration
8.3 Device configuration and configuration parameters in the TIA Portal
SIPLUS HCS4200 PROFINET/PROFIBUS DP
110
Operating Instructions, 07/2019, A5E35066204A/006
Configuration parameters POM4220 Highend
Description
Value range
Control type
(setting once per POM)
•
Half-wave control (default)
•
Half-wave control with soft start version 1
•
Half-wave control with soft start version 2
•
Half-wave control with adaptive soft start
•
Phase control
•
Phase control with soft start version 1
•
Phase control with soft start version 2
•
Phase angle control with adaptive soft start
Connection type
(setting once per POM)
•
Connection between phase and N-conductor
•
Connection between phase and phase
•
2-pin connection between phase and neutral conductor
•
2-pin connection between phase and phase
•
Economy circuit
1)
Phase LX1
2)
(setting once per POM)
•
Connected (default)
•
Not connected
Phase LX3
2)
(setting once per POM)
•
Connected (default)
•
Not connected
Soft start for each channel switch-on
operation
(setting once per POM)
•
No (default)
•
Yes
Enable output control
(setting once per POM)
•
No (default)
•
Yes
Enable fault current monitoring
(setting once per POM)
•
No (default)
•
Yes
Threshold for fault current monitoring
•
400 to 2000 mA
Response to errors
(setting per channel)
•
Channel substitute value 0 (default)
•
Channel value is retained
Parallel switching of loads
(setting per channel)
•
No (default)
•
Yes
Total power rating
(setting per channel)
•
400 ... 9600 W
Max. permitted deviation from total
power
(setting per channel)
•
50 ... 2000 W
1)
With the exception of the parameter "Response in the event of fault", all other parameter settings
are irrelevant for this type of connection.
2)
The parameters "Phase LX1" and "Phase LX3" are only relevant for connections between phase
and neutral conductor.