Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
117
8.5.2
Configuring
Requirements
Configuration control only works with PROFINET.
●
You need a CIM4210 PROFINET version V2.1 and higher.
Required steps
When configuring the CIM4210 in STEP 7 (TIA Portal), enable the "Configuration control on"
parameter.
8.5.3
Controller
8.5.3.1
Slot assignment
Slot assignment
The following table shows the possible slots for the various modules:
Table 8- 3
Slot assignment
Modules
Possible slots
Note
CIM PN
0
The PN connection of the CIM is not an element of
the configuration control.
CIM
1.1
The header of the CIM (subslot) is not an element
of the configuration control, but instead controls it.
PM
1.2
As a sub-slot part of the configuration control (han-
dled here as a slot 1).
POM
2 ... 25
Without empty slot directly after the CIM.
Summary of Contents for SIPLUS HCS Series
Page 1: ...SIPLUS HCS4200 PROFINET PROFIBUS DP ...
Page 2: ......