Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
119
Control data record
The table below shows the structure of a control data record with explanations of the
individual elements. The control data record can also be read back.
Table 8- 4
Structure of the simplified control data record V1.0
Byte
Element
Code
Explanation
0
Block length
4 +
maximum slot
Header
1
Block ID
196
2
Version
1
3
Version
0
4
Slot 1
of the station master
Slot assignment in the
station option
Control element
Contains information on which module
is inserted in which slot.
The value that you need to enter in the
corresponding byte depends on the
following rule:
•
If the module is included in the
station option, enter the slot num-
ber of the module from the station
master.
•
If the slot in the station master is
not allocated (e.g. empty slots as
part of combined operation), then
enter the slot number of the module
+ 128.
(Example: module as empty slot on
slot 3: Enter 131 in the control ele-
ment.)
•
If the module does not exist in the
station option, enter 0.
5
Slot 2
of the station master
Slot assignment in the
station option
...
...
...
28
Slot 25
of the station master
Slot order
8.5.3.3
Feedback data record
Operating principle
The feedback data record informs you about the accuracy of the module assignment and
gives you the option of detecting assignment errors in the control data record. The feedback
data record is mapped via a separate data record 197 V2.0. The feedback data record is
only processed with configured configuration control; otherwise it is rejected.