Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
122
Operating Instructions, 07/2019, A5E35066204A/006
Parameters of the RDREC instruction
Below, you will find explanations of individual parameters of the WRREC instruction which
you must supply with specific values in the configuration control context. You can find
additional information on the WRREC instruction in the STEP 7 online help.
ID
Hardware identifier
INDEX
Data record number: 197 (decimal)
RECORD
Feedback data record to read
For the structure of the control data record, see table. (Page 118)
In the event of an error, the RDREC instruction returns the following error messages via the
STATUS block parameter:
Table 8- 7
Error messages RDREC
Error code
Meaning
80B1
H
Invalid length; the length information in data record 197 is not correct.
80B5
H
Configuration control not configured
80B8
H
Parameter error
The following events cause a parameter error:
•
Incorrect block ID in the header (not equal to 197)
•
Invalid version identifier in the header
•
A reserved bit was set
•
Multiple slots in the station master are assigned to the same slot in the station
option
Special requirements relating to the transfer of the control data record
●
If you have enabled configuration control, the HCS is not ready for operation without a
control data record. As long as no valid control data record has been transferred, the I/O
modules are considered as failed by the CPU and exhibit substitute value behavior. The
CIM continues to be in data exchange.
●
The control data record is stored retentively in the CIM. Note:
–
If there have been no changes to the configuration, you do not need to rewrite the
control data record 196 during restart.
–
If you write a control data record with modified configuration to the CIM, it will result in
a reset of the HCS (station failure). The original data record 196 is deleted and the
new data record 196 is saved retentively. The station will then restart with the modified
configuration.