Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
129
The associated control data record DS196 must be pre-assigned as follows:
Byte
Element
Code
Description
0
Block length
4 + 25
Header
1
Block ID
196
2
Version
1
3
Version
0
4
Slot 1 of station master
0
PM is not available
5
Slot 2 of station master
2
POM available
6
Slot 3 of station master
0
PM not available
7
Slot 4 of station master
128 + 4
Free space due to combined
operation
8
Slot 5 of station master
128 + 5
Free space due to combined
operation
9
Slot 6 of station master
6
POM available
10
Slot 7 of station master
0
PM not available
11
Slot 8 of station master
0
Module not available
…
…
28
Slot 25 of station master
0
Module not available
The data record can also be written in abbreviated form with length 4+5; the last entry is
byte 8 in this case.
If there are no errors, the feedback data record DS197 contains the following entries:
Byte
Element
Code
Description
0
Block length
4 + 50
Header
1
Block ID
197
2
Version
2
3
Version
0
4
Slot 1 of station master
1
Module is actually not available
5
Slot 2 of station master
1
Module is actually available
6
Slot 3 of station master
1
Module is actually not available
7
Slot 4 of station master
1
Slot is empty
8
Slot 5 of station master
1
Slot is empty
9
Slot 6 of station master
1
Module is actually available
10
Slot 7 of station master
1
Module is actually not available
11
Slot 8 of station master
1
Module is actually not available
…
…
28
Slot 25 of station master
1
Module is actually not available
Summary of Contents for SIPLUS HCS Series