Functions
9.3 Power output control
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
141
9.3.10
Behavior of the power outputs
Parameterizable response
The response of the power outputs to an interruption in communication with the higher-level
controller can be defined. For each power output, the following can be parameterized:
●
Power output is "deactivated" (default).
●
The power output continues to operate with the most recent valid value.
Non-parameterizable, permanently defined response
The following events always result in deactivation of the power outputs:
●
Overtemperature
●
Failure of the 24 V supply voltage on the CIM or POM
●
Violation of the voltage range 207 V to 300 V or 253 V with POM4220 when at least one
POM4220 Low End is used (only with PM U/I).
●
Violation of the valid voltage range (Page 147)
●
Violation of the permitted frequency range for POM4220 Highend
Behavior during startup
The power outputs are "deactivated" until a connection to the higher-level controller has
been established and user data has been transferred.